Product Overview
SXFZ-III is five-in-one SF6 gas analyzer applied to measure dew point, purity and decomposition products of SF6 gas, which can detect three items by one testing,to save 2/3 of gas usage.
Features
♦ Light weight, portable.
♦ Fast measuring and gas conserving: after startup into the measuring state, the measuring time of dew point is about 5min; the measuring time of SF6 purity and SF6 decomposer is about 2min
♦ Auto locking: Adopts high quality auto lock joint made in German, no gas leakage, safe and reliable.
♦ Data storing: 200 groups’ data storage.
♦ Curve function: Large screen curve display the process of dew point measurement.
♦ Display clear: LCD screen, to display dew point, trace moisture (ppm), SF6 purity, SO2, H2S, CO and HF(option) content, environmental temperature, environmental humidity, time/date, battery capacity and etc.
♦ Build-in battery: 4Ah rechargeable lithium battery, continuously working 10 hours after one charging.

Specifications

Dew Point

Measuring Range

-60 ℃~+20 ℃

Measuring Precision

±1℃(-60℃~+20℃)

Measuring Duration(+20℃)

63% need 5S, 90% need 45S

(-60℃~+20℃)

63% need 10S,90% need 240S (+20℃~-60℃)

Purity

Measuring range:0%~100%

Accuracy:±0.5%

Measuring time:< 2min

H2S

Measuring range:0~100ppm

The minimum detectable amount:≤0.1ppm

Accuracy:±0.5%

Stability:0~100ppm

Repeatability:≤2%

SO2

Measuring range:0~100ppm

The minimum detectable amount:≤0.1ppm

Accuracy:±0.5%

Stability:0~100ppm

Repeatability:≤2%

HF(optional)

Measuring range:0~20ppm

The minimum detectable amount:≤0.01ppm

Accuracy:±0.5%

Stability:0~20ppm

Repeatability:≤2%

CO

Measuring range:0~1000ppm

The minimum detectable amount:≤1ppm

Accuracy:±0.5%

Stability:0~1000ppm

Repeatability:≤1.5%

Environmental Temperature

-40℃~+60℃

Environmental Humidity

0~100% RH

Power Source

AC 220V

Build-in rechargeable lithium battery

Battery Capacity

20 hours charging, 10 hours continuous working.

Working Temperature

-40℃~+80℃