Product Overview

SXYZ-2008 On-Load Tap-Changer Analyzer is designed to measure and analyze the electrical performance of on load tap changer of power transformers and special transformers.

Features

High precision

Light beam oscillograph function. SXYZ-2008 can simultaneous record A,B,C three phase, can auto catch and display transit resistance during transiting and the process of time changing.

To realize all the performance measurement on load tap changer. For example: switch selecting, break point, transit waveform, transit time, three phase synchronism and etc.

Comprehensive measured result analyzing: can analyze the resistance value of every point and every segment of waveform, every period of time and three phase synchronism and etc.

LCD screen, friendly English interface.

SD/SDMMC storage card: 0.5~2 G. Test data SD no limitation storage. And data in SD can be converted via SD-USB to upload to PC U disk.

Build-in thermal print.

Anti interference, wide working supply source range.

Compact designation, suitable for wild filed testing.

Specifications

Voltage Output

>20V

Working Supply

AC220V±10%,50Hz

Current Output

≥1A

Power

180W

Resistance Measuring Range

0.3~40Ω

Resistance Measuring Precision

0.1Ω~1Ω±0.1Ω,1Ω~40Ω±5%

(exclude1Ω)

Time Measuring Range

1ms~256ms

Time Measuring Recision

1ms~100ms±0.1ms

100ms~250ms±1%

3 Phase Synchronism

0.1ms

Sampling Rate

10~20KHz

Working Temperature

0~40℃

Working Humidity

≤80%RH