Test Object and Requirement:
The system is specially designed for AC withstand voltage test for 220KV and below voltage degree GIS, CT/PT, circuit breaker, switchgear and etc. Max. testing voltage is 550KV, testing frequency 30~300Hz, test object capacitance≤0.01uF.
Capacity Determination of the equipment:
8pcs Reactors will be designed, each reactor is 140kVA/70KV/2A/81H. Capacity amount is 1120kVA.
Determination:
Configurations of HV reactor, divider, variable frequency power generator and exciting transformer:
♦ HV reactors: 70kV/2A/81H/15min /8pieces in series applied on 220kV GIS voltage withstand testing.
♦ Divider: 550KV/1000PF (designed as three pieces, each piece rated at 187kV/3000PF). Three pieces used on high voltage measuring and system no-load resonant.
♦ Variable Frequency Power Generator: 50kW, input 220V/380V, output single phase 250V/500V. Full set power supply used to provide resistive loss of whole test circuit.
♦ Exciting transformer: 60kVA, input 500V, output 15KV, 30KV, used to increase the output voltage of variable frequency generator to applicable exciting voltage, and applied for reactor resonant.
No. | Name | Module No. & Specs | Quantity |
1 | Exciting Transformer | SXJB-60kVA/15KV/30kV | 1 set |
2 | Variable frequency power supply | SXBP-50kW/380V/220V | 1 set |
3 | HV Reactor | SXDK-140kVA/70kV | 8 pcs |
4 | Capacitive Divider | SXFR-550 kV -1000 pF | 1 set(3 pcs in series) |
5 | Connecting Cable | Accessories are as Table I. | 1 set |
6 | Factory Test Report |
| 1 copy |
7 | User's Guide |
| 1 copy |